Data and characteristics require

Relevant data and characteristics
 
Table -1: Structure data and characteristics
Parameters Comment Symbol Value
Dimensions (m) - Lb x Wb x Hb 40 x 20 x 25
Lightning flash density 1/km2/year Ng 4
Location factor Isolated Cd 1
LPS None PB 1
Shield at the structure boundary None KS1 1
Shield internal to structure None KS2 1
People present in the structure

Inside and outside the structure

 

nt 200
 
Table -2: Internal power systems and connected power line data and characteristics
Parameters Comment Symbol Value
Length (m) - Lc 200
Height (m) Aerial Hc 6
HV/LV transformer No Ct 1
Line location factor Isolated Cd 1
Line environment factor Rural Ce 1
Line shielding None PLD 1
PLI 0.4
Internal wiring precautions None KS3 1
Equipment withstand voltage Uw Uw = 2.5 kV KS4 0.6
Co-ordinated SPD protection None PSPD 1
End "a” line structure dimensions (m) None (Lb x Wb x Hb) -

Table -3: Internal telecom systems and connected TLC line data and characteristics
Parameters Comment Symbol Value
Soil resistivity ñ 250
Length (m) - Lc 1000
Height (m) Buried - -
Line location factor Isolated Cd 1
Line environment factor Rural Ce 1
Line shielding None PLD 1
PLI 1
Internal wiring precautions None KS3 1
Equipment withstand voltage Uw Uw = 1.5 kV KS4 1
Co-ordinated SPD protection None PSPD 1
End "a” line structure dimensions (m) None (Lb x Wb x Hb) -